Langelier Saturation Index Calculator

Find the saturation pH and Langelier index from measured pH, TDS, calcium hardness and alkalinity.

Chemistry and LabUpdated 2026-11-204 min read
Langelier Saturation Index Calculator
Enter calcium hardness as calcium carbonate, not elemental calcium.
Saturation pH
...
Langelier index...
Tendency...

What it does

The Langelier saturation index answers a practical question about water: will it lay down calcium carbonate scale, or will it try to dissolve it? Water that deposits scale can clog pipes, heaters and cooling towers. Water that is undersaturated can attack concrete and leave metal surfaces unprotected. The index turns a water analysis into a single number that describes that balance.

The calculation has two halves. The saturation pH is the pH at which the water would be exactly saturated with calcium carbonate at its current calcium, alkalinity, temperature and dissolved solids. The index is then the measured pH minus that saturation pH. A pH above saturation pushes carbonate toward solids, while a pH below saturation leaves the water hungry for carbonate.

The four correction terms have clear jobs. Dissolved solids raise the saturation pH slightly. Warmer water lowers it, because calcium carbonate is less soluble in warm water. Calcium hardness and alkalinity both lower it, since more of the ions that form scale means saturation is reached at a lower pH. The tool prints the saturation pH first so you can see the reference point before reading the index.

Choose metric or imperial units for the temperature input. The chemistry uses degrees Celsius, so an imperial entry in Fahrenheit is converted inside the tool. Dissolved solids, calcium hardness and alkalinity stay in mg/L in both modes, and calcium hardness and alkalinity must both be reported as calcium carbonate. Water labs normally print those units on the report, so the values can usually be copied across without conversion.

The index describes the calcium carbonate balance only. It is not a measurement of how fast a metal pipe will corrode, and it says nothing about chlorides, sulfate, dissolved oxygen or protective films. It is also a snapshot at one temperature. A water that is balanced in a cold supply line can become scale forming when heated in a boiler or a hot water tank, so check the index at the temperature where the water will actually sit.

How to use

  1. Choose the unit system for temperature: metric uses C and imperial uses F.
  2. Enter the measured pH from the same water sample as the mineral results.
  3. Enter total dissolved solids in mg/L.
  4. Enter calcium hardness and total alkalinity in mg/L as CaCO3.
  5. Enter the water temperature, using the unit shown on the form.
  6. Read the saturation pH, the index and the tendency label, then check the result at other temperatures if the water will be heated or cooled.

Formula

LSI = pH - pHs. pHs = (9.3 + A + B) - (C + D), where A = (log10(TDS) - 1)/10, B = -13.12 x log10(T + 273) + 34.55, C = log10(Ca) - 0.4 and D = log10(Alk).
pH
Measured pH of the water sample.
TDS
Total dissolved solids in mg/L.
T
Water temperature in degrees Celsius. Fahrenheit entries are converted first.
Ca
Calcium hardness in mg/L as CaCO3.
Alk
Total alkalinity in mg/L as CaCO3.
pHs
Saturation pH, the pH at which the water is balanced with calcium carbonate.

All logarithms are base 10, and the temperature term uses T + 273 with T in degrees Celsius. If your report gives elemental calcium rather than calcium hardness, convert it to mg/L as CaCO3 before using the tool. The index is a tendency indicator, not a rate. A value near zero is usually treated as balanced, and a band from about -0.3 to +0.3 is often called near neutral for practical water treatment.

Worked example

Example: pH 7.2, TDS 500, calcium 200 and alkalinity 200

Defaults: metric units, pH 7.2, TDS 500 mg/L, calcium hardness 200 mg/L as CaCO3, alkalinity 200 mg/L as CaCO3 and temperature 20 C.

  1. Find A: (log10(500) - 1) / 10 = (2.699 - 1) / 10 = 0.170.
  2. Find B: -13.12 x log10(20 + 273) + 34.55 = -13.12 x 2.4669 + 34.55 = 2.184.
  3. Find C: log10(200) - 0.4 = 2.301 - 0.4 = 1.901.
  4. Find D: log10(200) = 2.301.
  5. Combine them: pHs = (9.3 + 0.170 + 2.184) - (1.901 + 2.301) = 7.45.
  6. Subtract: LSI = 7.2 - 7.45 = -0.25, which the tool reports as Slightly corrosive.

Reference table

How the Langelier index is read in this calculator
IndexLabelCalcium carbonate tendency
Above 0.3ScalingWater tends to deposit calcium carbonate scale
0 to 0.3Near saturationClose to balance, with a mild scale forming tendency
-0.3 to 0Slightly corrosiveClose to balance, with a mild dissolving tendency
Below -0.3CorrosiveWater tends to dissolve calcium carbonate

Limits

  • Describes calcium carbonate only, not the corrosion rate of steel, copper or other metals.
  • Uses one temperature at a time, so a result at 20 C does not describe the same water in a hot tank.
  • Requires calcium hardness and alkalinity as mg/L as CaCO3, so reports in other units must be converted first.
  • Does not account for inhibitors, antiscalants, dissolved oxygen or protective films that change real behaviour.

Common mistakes

  • Entering elemental calcium in mg/L instead of calcium hardness as CaCO3.
  • Using a pH measured on a different sample or at a different point in the system.
  • Reading a negative index as proof that no scale can form anywhere in the system.
  • Forgetting to switch temperature units when the report is in Fahrenheit and the form is set to metric.
  • Treating a near zero index as a full corrosion assessment.

Try it yourself

Quick checks. Answers sit tucked under each question.

With pH 8.0, TDS 500, calcium 200, alkalinity 200 and 20 C, what does the tool show?

The saturation pH is still 7.45. LSI = 8.0 - 7.45 = 0.55, so the tool shows 7.45, 0.55 and Scaling.

The same water at pH 7.2 is cooled to 0 C. What happens to the index?

Cooling raises the saturation pH to 7.86, so LSI = 7.2 - 7.86 = -0.66. The tool shows Corrosive, a stronger dissolving tendency than at 20 C.

Raise TDS to 1000 mg/L and keep pH 7.2, calcium 200, alkalinity 200 and 20 C. What is the index?

The larger TDS term gives a saturation pH of 7.48. LSI = 7.2 - 7.48 = -0.28, so the tool reports Slightly corrosive.

Questions

What does a positive Langelier index mean?

The water is above its saturation pH and tends to deposit calcium carbonate scale. The higher the positive value, the stronger the tendency.

What does a negative index mean?

The water is below saturation and can dissolve calcium carbonate. That can strip protective deposits, though it does not by itself predict metal corrosion.

Why must calcium be reported as CaCO3?

The constants in the formula were derived with hardness and alkalinity both expressed as calcium carbonate. Elemental calcium values are about 2.5 times smaller and must be converted first.

Does temperature matter?

Yes. Calcium carbonate is less soluble in warm water, so the saturation pH falls as temperature rises and the same measured water can move toward scaling when heated.

Is an index of zero perfectly safe?

It means the water is balanced with respect to calcium carbonate. Other factors such as chloride, dissolved oxygen and flow still affect real systems.

Can I use this on seawater or brine?

Not reliably. The formula is a fresh water and low salinity approximation. High ionic strength waters need activity based models outside this tool.

Sources

How this page was checked. The formula above was matched against the cited sources, and the worked example was run through the tool on this page before publishing. If you spot an error, contact us so we can fix it and note the correction.