Extension Cord Size Calculator

Minimum AWG cord gauge from tool amps and cord length.

Home and DIYUpdated 2026-10-112 min read
Extension Cord Size Calculator
Minimum gauge
...
Duty class...
Voltage drop...

What it does

Extension cords starve motors when undersized: thin wire over long runs drops voltage, heats up, and stalls saws. Gauge must rise with amps and with feet together, which is why a 25 ft lamp cord fails a 100 ft saw.

The tool above takes tool amps with cord length in feet or meters. It returns minimum AWG with duty class and voltage drop beside it. The default 15 A over 100 ft needs 10 AWG extra heavy duty at about 3.73 V (3.1%) drop.

Tables match university safety charts drawn from NEC lineage: 16 gauge to 13 A, 14 to 15 A, 12 to 20 A at short lengths, stepping up per length band. Voltage drop math through copper resistivity confirms the edges, with 5% as the design budget and 3% preferred for motors.

Temporary use rules close the loop. One portable appliance plugs straight into the wall, never daisy chained, on UL listed cord rated for indoor or outdoor duty, and permanent loads get wired circuits instead.

How to use

  1. Read tool amps from its plate.
  2. Pick the full cord run length.
  3. Read minimum AWG first, never thinner.
  4. Check drop stays inside 5%.
  5. Use outdoor W rated cord outside.
  6. Retire nicked, hot, or stiff cords.

Formula

Lookup by amps x length band. Drop = 2 x 12.9 x amps x feet / circular mils. Budget 5% of 120 V.
AWG
Wire gauge; lower number is thicker.
12.9
Copper K factor in ohm circular mil per foot.
5%
Round trip drop budget, 6 V at 120 V.

Meters convert first (divide by 0.3048) into the foot band table. Above 20 A the answer is a permanent circuit, not a cord.

Worked example

Example: 15 A, 100 ft

Imperial defaults: 15 A, 100 ft.

  1. Band: 100 ft row, 12 to 15 A column.
  2. Gauge: 10 AWG minimum.
  3. Drop: 2 x 12.9 x 15 x 100 / 10,380 = 3.73 V.
  4. Percent: 3.73 / 120 = 3.1%, inside budget.
  5. 14 AWG would drop 9.42 V (7.8%), rejected.
  6. Tool shows 10 AWG, extra heavy duty, 3.73 V (3.1%).

Reference table

Minimum gauge by amps and length
Length7 to 10 A10 to 12 A12 to 15 A
25 ft16 ga14 ga14 ga
50 ft14 ga14 ga12 ga
100 ft12 ga12 ga10 ga
150 ft, 12 to 15 A12 ga at 10 A10 ga at 12 A8 ga

Limits

  • 120 V portable tools; 240 V differs.
  • Copper only; aluminum needs other tables.
  • Coiled cords trap heat; uncoil fully.
  • Table bands, not continuous interpolation.

Common mistakes

  • Reading higher AWG as thicker.
  • Running 100 ft on a 25 ft rated cord.
  • Daisy chaining two cords.
  • Permanent shop loads on cords.
  • Indoor cord in rain.

Try it yourself

Quick checks. Answers sit tucked under each question.

10 A, 50 ft?

14 AWG minimum, medium duty.

7 A, 25 ft?

16 AWG minimum, light duty.

25 A tools?

Rejected: above 20 A, wire a permanent circuit.

Questions

Default cord?

10 AWG minimum for 15 A at 100 ft.

Bigger number thicker?

No: lower AWG is thicker wire.

Acceptable drop?

Inside 5% at 120 V; motors prefer 3%.

Two cords joined?

Never daisy chain; buy one full length cord.

Outdoor cord?

W rated, UL listed for outdoor duty.

Metric match?

Yes: 30.48 m converts to the same 100 ft band.

Sources

How this page was checked. The formula above was matched against the cited sources, and the worked example was run through the tool on this page before publishing. If you spot an error, contact us so we can fix it and note the correction.